EtherCAT Master i950 reports warning "Fieldbus: Invalid process data", warning message cannot be reset (corrected from V01.05.02)

Corrected from:
Servo-Inverter i950 FW:  from  V01.05.02.1788
 
Response of the new Version:
After starting the i950 no error message "Fieldbus: Invalid process data", ID: 0x31038193, severity "Warning" is now entered in the logbook.
Monitoring is now only active when the EtherCAT status 0x2368 = "Operational [8]" is reached.

 
What happens?
After starting the i950 with default values the error message "Fieldbus: Invalid process data", ID: 0x31038193, Severity "Warning" is entered in the logbook.

When does the behaviour occur?
When an EtherCat module is plugged in and the EtherCAT status is not 0x2368:0 = "Operational [8]".  

Which products are affected?
Servo inverter i950 FW
 
Short-term measures / evaluation / recommendations:
Deactivate the EtherCAT monitoring. Set the error response to 0x2859:5 = "No response [0]".


Automatic Translation

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202000014/1/