TM TemperatureControl: Monitoring SensorMonitoringValue cannot be deactivated (eliminated from V3.20.0)

Corrected from:
Documentation for Technology Module Temperature Control as of V3.20.0
Response of the new version:
The documentation has been corrected.
 
What happens?
The documentation contains incorrect values for deactivating sensor monitoring. The values are lrSensorMonitoringValueMin = -1000 and lrSensorMonitoringValueMax = -1000 for deactivating the limits. These values do not deactivate sensor monitoring. An error is generated when the value is exceeded.
 
When does the behaviour occur?
If the values lrSensorMonitoringValueMin = -1000 and lrSensorMonitoringValueMax = -1000 have been set to deactivate sensor monitoring.
 
Which products are affected?
Function block L_TP2P_TemperatureControlBase from library L_TP2P_TechModulesProcessFunctions
 
Short-term measures:
To deactivate sensor monitoring, the values can be set to lrSensorMonitoringValueMin = -32768 and lrSensorMonitoringValueMax = 32767.

Automatic Translation

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201900231/1/