Station alias (second station address) is saved with mains failure protection

Corrected from:
EtherCAT E94AYCET communication module FV 4.02
 
Response of the new version?
If the station alias is allocated via the EtherCAT master and therefore directly via EtherCAT, the station alias is saved with mains failure protection in the EEPROM of the EtherCAT module. Therefore the new EtherCAT V4 module can also be used without any restrictions in a Lenze controller modular machine configuration (MMC) for EtherCAT.
 
What happens?
The previous module V3 could not be used with the Lenze controller modular machine configuration (MMC) function for EtherCAT.

When does the problem occur?
So far, the problem has occurred when the station alias was directly allocated via the EtherCAT master.

Which products are affected?
EtherCAT E94AYCET communication module FV 3, 2 and 1

Diagnostics options?
If the default station alias is shown after mains switching, this malfunction occurs.

Short-term measures/recommendations?
The station alias can be predefined and saved with mains failure protection directly via the Lenze code 1x899.

Evaluation:
None