L_MC2P_TappetRegister: FAST IO output does not switch if tappet is already occupied when it is activated (corrected from V3.14.1)

Corrected from:
Library:   L_MC2P_MotionControlCam  (FAST Motion)  V03.14.01.00
                        (update via Package Manager)
 
Response of the new version:
L_MC2P_TappetRegister FB: The Fast IO output switches correctly, even at standstill.
 
What happens?
The Fast IO output or xSwitch are not set although the tappet position has been reached and the output would have to be activated.   
 
When does this behaviour occur?
The behaviour occurs if the xEnable input of the 'L_MC2P_TappetRegister' FB is set and the axis is at standstill.

Which products are affected?
Library:  L_MC2P_MotionControlCam  (FAST Motion)
                        (contained in the PLC Designer) 
 
Short-term measures:
Only activate the L_MC2P_TappetRegister FB at standstill when being outside the cam position.
 
Evaluation/recommendations:
 