CAN on board life guarding error cannot be reset

Corrected from:
  • 9400 HighLine V13.01.06
  • 9400 Servo PLC V07.01.06
Response of the new version:
Life guarding errors can be reset.
 
What happens?
After executing CAN reset node, a life guarding error continues to be displayed in C166 although it no longer exists (C345: No error).
 
When does this behaviour occur?
The behaviour occurs if the 9400 has been configured as a node guarding slave, the condition for a life guarding error has been met once (e.g. life guarding telegram stopped by the master) and CAN reset node is executed.
 
Which products are affected? 
  • 9400 HighLine < V13.01.06
  • 9400 Servo PLC < V07.01.06 
Short-term measures:
Restart device.
 
Evaluation/recommendations:
Limited diagnostics options.
 

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201600573/1/