L-force Motion - Limited measuring system: Actual position step change due to overflow at display range limit (no correction planned)

Corrected from:
Library:  L_SM3_...   (L-force Motion)    (no correction planned)
Response of the new version:
 
 
What happens?
The incremental actual position (32 bits) of the drive overflows after a certain number of revolutions.
This leads to an actual position step change.
 
When does this behaviour occur?
The behaviour occurs when using axes in a limited measuring system which are continuously traversing in one direction.
 
Which products are affected?
Library:  L_SM3_...   (L-force Motion)
 
Short-term measures:
If necessary, convert the project from L-force Motion to the new product FAST Motion.
With FAST Motion, the described behaviour does not occur.
 
Evaluation/recommendations:
Since FAST Motion replaces the previous product L-force Motion, there are no more changes/enhancements planned for L-force Motion.
  
 