L_TT1P_TablePositioning: Wrong profile data (corrected from V3.13)

Corrected from:
L_TT1P_TechnologyModules_LM V3.13.0.7
 
Response of the new version:
Positioning is aborted during sequence profile processing (profile <> eProfileNumber input).
After this, the xExecutePositioning input is only set to TRUE for one cycle.
In this case, positioning will be executed with the data saved in eProfileNumber (profile data set selection). 
What happens?
The TablePositioning technology module works with wrong profile data. 
 
When does this behaviour occur?
The behaviour occurs when aborting a positioning process during sequence profile processing (profile <> eProfileNumber input) and
the xExecutePositioning input is only set to TRUE for one cycle after this.
In this case, positioning will not be executed with the data saved in eProfileNumber (selection of the profile data set), but the previously aborted profile will be executed.
 
Which products are affected?
L_TT1P_TablePositioning function block from the L_TT1P_TechnologyModules_LM library (V3.12.0.9 and higher)
 
Short-term measures:
The xExecutePositioning input must be set for at least two cycles.
 

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201500847/1/