Configurable status outputs at the L_MckStateInterface

Function extension:

8 boolean status outputs have been added to the L_MckControlInterface. The status to be indicated can be set in C1293/1..8.

Example:

bOperationState5 shall return TRUE if "Positioning" is selected as current operating mode, the drive is referenced and the MCK is ready to execute start signals. For this, C1293/005 has to be configured as follows:

C1293/005 …

  • Bit00: ActOpModeBit00       = TRUE
  • Bit01: ActOpModeBit01       = TRUE
  • Bit02: ActOpModeBit02       = FALSE
  • Bit03: ActOpModeBit03       = FALSE
  • Bit04: Busy                              = FALSE
  • Bit05: Done                             = FALSE
  • Bit06: HomPosAvailable       = TRUE
  • Bit07: ReadyToOperate        = TRUE
 
Contained in which products?
  • Inverter Drives 8400 TopLine V16.00.00
 
Application:
Application-adapted handshake for master-slave operation or for higher-level control via only one status bit.