L_MC1P: 'Quick stop option code' parameter (0x605A) is overwritten during initialisation (corrected from V3.10.0)

Corrected from:
- Library: L_MC1P_MotionControlBasic (FAST Motion) V03.10.00.00
  (contained in PLC Designer V03.10.00.00 and higher)
 
Response of the new version:
The parameter (0x605A) continues to be overwritten by the Axis_Ref in the initialisation phase.
You can, however, use the 'L_MC1P_SetQuickStopOption' FB to change the parameter (0x605A) via the controller application.
 

What happens?
In the initialisation phase, the controller parameter (0x605A) for selecting the response to quick stop is overwritten by the Axis_Ref. 
In the end, the "--> Remain in 'Quick stop active' device state" setting (0x605A=6) will always be active.
When does this behaviour occur?
Always.
 
Which products are affected?
- Library: L_MC1P_MotionControlBasic (FAST Motion)
  (contained in the PLC Designer)
 
Short-term measures:
 
Evaluation/recommendations: