Rotation test mode: Current/frequency (0x2825=2): Starting angle 0x2528:3 is not accepted correctly (corrected from V1.5.6)

Corrected from:
- i700 servo inverter V01.05.06.9665

Response of the new version:
For the 'Rotation test mode: Current/frequency' (0x2825=2), the corresponding starting angle is now always loaded correctly under 0x2528:3.


What happens?
As starting angle for the rotation test mode: Current/frequency (0x2825=2), erroneously, the last angle available of the pole position identification (PPI) (360°) is used.

When does the problem occur? 
The problem occurs when using the rotation test mode: Current/frequency (0x2825=2) after a pole position identification (PPI) (360°).

Which products are affected?
- i700 servo inverter ≤ V01.04.00.9125

Short-term measures/recommendations:
None.

Evaluation:
The function restriction is not relevant for normal system operation.
 