Adjustable delay time for IMax status

Which products are affected?
Inverter Drives 8400 StateLine, HighLine, and TopLine from firmware version 12.00.00.00

Functional description
In C983, a delay time of 0-1000ms for the 'Current setpoint in the limitation' status signal LS_MotorInterface_bLimCurrentSetVal can be set. The Lenze setting is C983=50ms.

Applications
Avoiding of a toggle bit when the current limitation only responds for a very short time.
With the setting C983=0ms, the monitoring acts compatibly to the versions
StateLine+HighLine < 11.0, and TopLine <2.0.