EtherCAT module signals ¨internal error¨

Corrected from:
EtherCAT E94AYCET Firmware Version 3.00 communication module

Behaviour of the new version?
The module does not signal an internal error when the controller synchronisation C01120 is set without an EtherCAT master being connected.



What happens?
Under certain conditions, the module signals an 'internal error' when the controller synchronisation C01120 is activated.

When does the problem occur?
The problem occurs in the following 2 scenarios:

1.
- no EtherCAT master connected
- setting C01120 from off to MXI1 or MXI2
=> module signals an internal error with the error response 'information'

2.
- no EtherCAT master connected
- setting C01120 from off to MXI1 or MXI2
- saving the parameter set and mains switching
=> module signals an 'internal error' with the error response 'information'

Which products are affected?
EtherCAT E94AYCET FV 2.0 communication module
EtherCAT E94AYCET FV 1.01 communication module

Diagnostics options?
In the 9400 logbook, the following message appears:
EtherCAT communication module, internal error, response 'information'

Short-term measures/recommendations?
None