Event-controlled transmission of Tx PDOs with cyclic superimposition (eliminated from V2.0 onwards)

Eliminated from:
CANopen bus coupler EPM-S110 Firmware V2.0

Behaviour of the new version?
According to the transmission type selected (index I-180x, subcode 2, value 255) the PDOs are transmitted in an event-controlled way with superimposed cycle time.



What happens?
If the event-controlled PDO with superimposed cycle time is selected (index I-180x, subcode 2, value 255) the PDOs are only transmitted cyclically.

When does the problem occur?
If transmission type 255 has been selected as PDO in index I-180x, subcode 2.

Which products are affected?
CANopen bus coupler EPM-S110 Firmware V0.1
CANopen bus coupler EPM-S110 Firmware V0.2
CANopen bus coupler EPM-S110 Firmware V1.1

Possible diagnostics?
The behaviour has occurred if the PDO is not transmitted in case of an event change in the user data.

Short-term measures/recommendations?
None.