Operation not possible in case of cycle times => 4 ms

Eliminated from:
EtherCAT E94AYCET FV 2.00 communication module

Behaviour of the new version?
Operation including all available cycle times of the EtherCAT system is possible.




What is the reaction?
During operation including cycle times >= 4 ms, problems in parameter communication or mapping may occur.

When does the problem occur?
The problem may occur when cycle times => 4 ms and a number of slaves => are involved.

Which products are affected?
EtherCAT E94AYCET FV 1.01 communication module

Diagnostics options?
In the event of an error, the EtherCAT system cannot be started.

Short-term measures/recommendations?
None

Information taken from chapter 1.1.9 of Service Message No. 44/2009.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200910938/1/