Functional description
Both temperature values are displayed simultaneously via two new codes, C1200/1 (Temperature feedback via resolver interface X7) and C1200/2 (Temperature feedback via encoder interface X8). The value shown in C1200/x does not depend on which of the temperature evaluations (via X7 or X8) is used to disconnect the drive.
On a related note, code C1193 has been expanded to include selection 5 ('X7 and X8 parallel'). To ensure that both sensors are evaluated, C1193 must be set to 5. Only then will the higher of the two measured values be displayed under C0063. The motor's overtemperature monitoring function will then also refer to this value.
Applications
Applications with more than one temperature feedback function, e.g. when two asynchronous motors are operated on one controller
Contained in which products/versions?
All 9400 HighLine axis controllers with firmware version 07.00.30.00 or higher