Preinitialised motor data (from V2.0 onwards)

Function extension:
The default setting now contains the preinitialised motor data values which are designed for a motor adapted to the frequency inverter's power. As a result, the ideal values for the 'VFCplus' operating modes are stored, and quick commissioning of the 'SLVC' operating mode becomes possible without a motor identification run.

The following codes are now preinitialised in relation to the device power:

Codestelle     Function
L-C00016       Umin boost
L-C00021       Slip compensation
L-C00081       Rated motor power
L-C00082       Motor rotor resistance
L-C00084       Motor stator resistance
L-C00085       Motor stator leakage inductance
L-C00087       Rated motor speed
L-C00088       Rated motor current
L-C00089       Rated motor frequency
L-C00090       Rated motor voltage
L-C00091       Motor cosine phi
L-C00092       Motor magnetising inductance
L-C00095       Motor magnetising current

In which products/versions is it included?
8400 StateLine  SW V2.0 onwards

Applications
Operating mode 'SLVC'

Published with service message No. 2008/26

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200804524/1/