Incomplete basic configuration C0005 = 111xx in the signal flow

Which products are affected?
EVS93xx-EK V7.1, EVS93xx-CK V7.1

What happens?
The drive does not run although the controller is enabled and the cam profile data has been parameterised correctly.

When does the problem occur?
The problem occurs if a basic configuration C0005 = 111xx is used.

Possible diagnostics?
The behaviour can be detected by checking code C0937. If under C0937 a value is parameterised unequal 13301 the set velocity of the CDATA function block is not evaluated and 'idles'.

Short-term measures/recommendations?
Insert the missing signal connection manually (C0937 = 13301). Moreover, set the y-stretching /compression mode to asynchronous stretching/compression (C1313 = 0).

Evaluation:
The basic configurations C0005 = 111xx are used vary rarely. The behaviour is immediately detected during initial commissioning and can quickly be eliminated by applying the procedure described under Short-term measures/recommendations.