CAN reset node via code C0358 not able to be executed via CAN access (remedied from V7.0 in 9300ES, from V8.0 in 9300EP and from V8.1 in 9300EK, EV)

Which products are affected?
9300ES servo controller V7.0
9300EP position controllers as of V8.0
9300EV vector inverter (0.37..90kW) V8.1
9300EK cam profiler as of V8.1

Eliminated function restriction
Now a CAN reset node via code C0358 is possible by means of writing via the on-board-CAN-bus (X4), in order to transfer the participant to the 'Operational' status.




Which products are affected?
9300 ES servo controller <= V6.2
EVS93xx-EK V7.1, EVS93xx-CK V7.1

What happens?
A CAN reset node via code C0358 is not possible by means of writing via the on-board-CAN-bus (X4).

When does the problem occur?
When writing on code C0358 for executing a reset node via the CAN bus itself.

Possible diagnostics?
After writing the reset node is not executed and the participant remains in status 'pre-operational'.

Short-term measures/recommendations?
Execute reset node by mains switching.

Evaluation:
A reset node for activating the process data communication can also be realized in an alternative way.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200701904/1/