No controller inhibit in case of a control reset

Which products are affected?
ECS axis module ECSxx series, operating software V6.7
EVS93xxEI (Servo PLC V6.5)
EVS93xxET (Servo PLC V6.5 equipped with technology function)

What happens?
In case of a control reset, e. g. via the DDS menu Online>Reset or code C2108 = 3, the drive is stopped but remains in control mode (controller enable).

When does the problem occur?
Irrespective of the exceptional response set (DDS menu Project>Exceptional response) the drive is stopped but not inhibited. According to standard the exceptional response is set to controller inhibit (CINH).

If the PLC program is stopped, e. g. via the DDS menu Online>Stop or code C2108 = 2, the drive responds according to the exceptional response set.

Possible diagnostics?
None.

Short-term measures/recommendations?
None.

Evaluation:
In case of a control reset the drive does not respond according to the exceptional behaviour set. The drive is always stopped but remains enabled. This behaviour can be detected during commissioning phase. A control reset is usually not executed while the machine is running.