Faulty JOG values in case of the 8200 vector/motec with Application I/O due to parameter setting in offline mode (remedied from V4.8)

Remedied from?
GDC 4.8, GDC 4.8 Update and GDC easy in combination with 8200 vector/motec and Application I/O

Behaviour of the new version?
The parameter setting of the codes with regard to the JOG values (L-C0037, L-C0038, L-C0039, L-C440/1, L-C440/2 and L-C440/3) can be carried out in offline mode without any restrictions.



Which products are affected?
GDC 4.7 in combination with an 8200 vector/motec and Application I/O when set the parameters of JOG values offline.

What happens?
When the parameter setting for 8200 vector or 8200 motec makes, it is not possible in offline mode to adjust the right JOG values (JOG1 to JOG3) and acceleration and deceleration ramp times.
If JOG values are entered under the codes L-C0037, L-C0038 and L-C0039 these values are copied internally to codes L-C0440/1, L-C0440/2 and L-C0440/3 of the Application I/O. Decimal codes of the JOG values are not transferred. When correcting the values under the codes L-C0440/1, L-C0440/2 and L-C0440/3 another internal copy is made but the decimal codes are not considered either (the decimal will set to zero). A comparison of codes C0037 to C0039 with C0440 shows the differences.

Note: In online mode the parameter setting is correct!

When does the problem occur?
When parameterising the codes L-C0037, L-C0038, L-C0039, L-C0440/1, L-C0440/2 and L-C0440/3 in offline mode.

Possible diagnostics?
If values are entered under the codes L-C0037, L-C0038 and L-C0039 the codes L-C0440/1, L-C0440/2 and L-C0440/3 can be used to check if the correct values have been entered.

Short-term measures/recommendations?
This problem does not occur when setting the parameters of the codes mentioned above in online mode.

Evaluation:
If the decimal codes are not considered, the drive may use wrong JOG values.