Reset (original) does not delete Application RAM 1 and 2 (elimination)

Which products are affected?
EPL-10200 (Drive PLC V7.x, hardware version 2B)
EPL-10201 (Drive PLC V7.x, hardware version 2B with Extension Board 1)

Eliminated function restriction
Lenze PLCs offer the opportunity to copy parts of the variable memory of the PLC (e. g. global variables or arrays) into a 'backup memory'. As a result, e. g. recipe memories or measured-value memories can be implemented. Application RAM 1 and 2 represent this 'backup memory' and can be written and read by means of functions of the LenzeMemDrv.lib.
After mains connection or 'Reset original' the data under Application RAM 1 and 2 were not deleted – the content was not defined.

After mains connection or 'Reset original' the data under Application RAM 1 and 2 are correctly set to zero.
 
 
Which products are affected? 
EPL-10200 (Drive PLC V6.3 - V6.5)

What happens?
Application RAMs 1 and 2 have not been set to zero. There is still some data in the memory left.

When does the problem occur?
During mains connection or if a reset (original) is executed.

Possible diagnostics?
None.

Short-term measures/recommendations?
Delete the RAMs mentioned above manually.

Evaluation:
A manual deleting of the application data is required.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200503193/1/