PTC input as DIGIN

Application:

Additional digital input, e.g. manual/remote – changeover with bus operation

Description

At 8200 vector/motec software version V2.1 with Standard I/O or Field bus module can the PTC input be configured as follows:
  • C0410/x = 7
  • C0415/x = 38
  • C0417/x= 38
  • C0418/x = 38

The input is
  • active, if PTC input T1 and T2 are open or if the input voltage is > UB20 (reference GND2) at T1
  • not active, if PTC input T1 and T2 are closed or at T1 = GND2