Question:
Which meaning have ErPxx error messages which are not described in more detail in the product documentation of the 8200motec/vector?
Answer:
ErP 00: Basic device does not accept the component part (e.g. 8212 from the software ID number 82S8212V_14000) of the software ID number in the parameter set of the keypad.
Reason: The software version of the basic device is lower than the one of the data set inside the keypad (e.g. the keypad is parameterised with a basic device software 2.x but the basic device has a software version SW 1.x).
ErP 01: Transfer of basic device parameter set 1 is aborted
Reason: The data of the basic device parameter set 1 are not correct (e.g. faulty data storage in the keypad; data in the keypad were created on another controller).
ErP 02: Transfer of basic device parameter set 2 is aborted
Reason: The data of the basic device parameter set 2 are not correct (e.g. faulty data storage in the keypad; data in the keypad were created on another controller).
ErP 03: Transfer of basic device parameter set 3 is aborted
Reason: The data of the basic device parameter set 3 are not correct (e.g. faulty data storage in the keypad; data in the keypad were created on another controller).
ErP 04: Transfer of basic device parameter set 4 is aborted
Reason: The data of the basic device parameter set 4 are not correct (e.g. faulty data storage in the keypad; data in the keypad were created on another controller).
ErP 07: Basic device does not accept the length of the basic device parameter set.
Reason: The parameter set in the keypad has a wrong length and is therefore not accepted by the basic device.
ErP 08: Checksum error in the parameter set storage of the basic device paramater set of the keypad.
Reason: Faulty data storage in the keypad.
ErP 09: AIF communication error detected in the keypad while transferring the parameter set.
Reason: Contact problem at the AIF interface.
ErP 10: Function module does not accept the component part (e.g. AFA0 from the software ID number 82SAFA0B_14000) of the software ID number in the parameter set of the keypad.
Reason: The software version of the function module is lower than the one of the data set inside the keypad (e.g. the keypad is parameterised with a function module software 2.x but the function module has a software version SW 1.x).
ErP 11: Transfer of parameter set 1 of the function module is aborted
Reason: The data of the parameter set 1 of the function module are not correct (e.g. faulty data storage in the keypad; data in the keypad were created on another device).
ErP 12: Transfer of parameter set 2 of the function module is aborted
Reason: The data of the parameter set 2 of the function module are not correct (e.g. faulty data storage in the keypad; data in the keypad were created on another device).
ErP 13: Transfer of parameter set 3 of the function module is aborted
Reason: The data of the parameter set 3 of the function module are not correct (e.g. faulty data storage in the keypad; data in the keypad were created on another device).
ErP 14: Transfer of parameter set 4 of the function module is aborted
Reason: The data of the parameter set 4 of the function module are not correct (e.g. faulty data storage in the keypad; data in the keypad were created on another device).
ErP 17: Function module does not accept the parameter set length of the function module.
Reason: The parameter set in the keypad has a wrong length and is therefore not accepted by the function module.
ErP 18: Checksum error in the parameter set storage of the function module parameter set of the keypad.
Reason: Faulty data storage in the keypad.
ErP 19: AIF communication error in the keypad detected while transferring parameter sets.
Reason: Contact problems at the AIF interface.