Question:

How can the process data communication of the Profibus DP be monitored for 8200 vector/motec?

Answer:

In the E82ZAFPC and E82ZAFPC201 Profibus DP field bus function module for 8200 vector / 8200 motec there is the L-C1514 code digit, with which the process data monitoring of the profibus can be set. In the Lenze factory default setting this monitoring is not active.

Value range of code digit C1514:
  • 0: No reaction (Lenze factory default setting)
  • 1: TRIP (interference)
  • 2: CINH (controller inhibit)
  • 3: QSP (quick stop)

The process data monitoring time belonging to the monitoring function is preselected by the Profibus master. In code digit C1513 of the 8200 drive controller it can only be displayed. If the Profibus DP module does not receive any new data in this process data monitoring time, the reaction selected in code digit C1514 will be enabled at the 8200 vector/motec drive controller.

Compare the monitoring function of the profibua module 2133 for controller 9300 and 8200 vector/motec in article 20020215.