Question:
How can be avoided that, in case of intermediate circuit overvoltage, the brake is ventilated several times / activated by the dynamic message overvoltage?
Answer:
In case of overvoltage a TRIP can be generated by the help of the service code digit C0310, Bit 0 = 1 (from SW2.1 adjustable with keypad). Via the code digit C0415/01= 18 the relay-K1 is adjusted to DCTRL1-TRIP or Qmin or IMP and the brake is driven in case of overvoltage.