Behaviour of the new version?
A change of the DIP switch does not cause any responses after the Gateway firmware has been booted.
Which products are affected?
EPM-T110 (CAN Gateway V1.3)
EPM-T111 (CAN Gateway ECO V1.3)
What happens?
The Gateway indicates an error.
When does the problem occur?
Vibrations may cause the DIP switch to bounce. A temporarily resulting change of the DIP switch position has immediately been accepted while the system was running. As a result, the faulty behaviour occurred.
Possible diagnostics?
If the error has occurred the module LEDS 'ER, BA and RD' are blinking alternately in a 1 Hz cycle.
Short-term measures/recommendations?
The module status could be changed back to operational by switching the module off/on.