Application error cannot be reset without using a control (remedied from V1.2)
Remedied from:
ECS Motion V1.2
Behaviour of new version?
An application error (error number > 400) can always be reset. Regarding this it is not important if the reset is executed via the control or alternatively via GDC or keypad.
Which products are affected?
ECSxM V1.1
What happens?
An application error (error number > 400) cannot be reset without a connected control.
When does the problem occur?
If the drive is in the quick stop (QSP) state and an application error (error number > 400) has occurred in addition, the TRIP cannot be reset via code C0043 (e. g. via GDC). A reset is only possible via the control by means of a control word.
Possible diagnostics?
Online diagnostics via GDC or keypad
Short-term measures/recommendations?
Reset the TRIP via the control or by mains switching.
Evaluation:
Since the ECS Motion cannot be operated without a control, this error may in worst case only lead to slight delays at the beginning of the commissioning.
Published with service message No. 2007/38 und 2007/39
Taxonomy:
ECSxA application
,
ECSxE power supply module
,
ECSxK capacitor module
,
ECSxM motion
,
ECSxP position and shaft
,
ECSxS speed and torque
,
ECS servo inverters
AKB-ID:
200706246
Last update:
2023/09/08
Category:
Informations sur la version
Lenze reserves the right to change information on this page at any time. Any liability for the accuracy of the information is excluded.