L_TV2P_StackerCrane: Deadlock if the TM is activated too quickly (corrected from V3.30.0)
Removed from:
L_TV2P_TechModulesStackerCrane (as of V3.30.0). (Update via Easy Package Manager)
Behavior of the new version:
The y-axis runs the profile, even if the input xExecuteProfile for 1x PLC cycle is set to FALSE and then TRUE again.
Description of behavior:
The y-axis does not move.
Conditions under which the behavior occurs:
The x and y axes are moved in the coordinated mode
The xExecuteProfile input for both technology modules is set to FALSE for 1xSPS cycle and then TRUE again.
Affected products:
Library L_TV2P_TechModulesStackerCrane
Short-term measures: The input xExecuteProfile must remain FALSE for at least 2x PLC cycles before the next rising edge of the next profile is requested.
Recommendations, Rating: In the coordinated mode of the profiles, profile data is exchanged between the x and y axes. In this mode, no rising edge of the input xExecuteProfile is recognized for the y-axis if it is only set to FALSE once in the PLC cycle. With the consideration of the short-term measure, the function is given and the profiles are executed.