L_MC1P: MC_Touchprobe: TP detection for i750 servo inverter inaccurate (fixed from use of the new i750 device description V01.01.00.03)

Removed from:
i750 and PLC-Designer with new i750 device description V01.01.00.03
How the new version behaves:
The touch probe detection and TP position calculation now work, using the new device description,  as expected.
Important:
In order for the new device description to be used and the correction to take effect, the i750 axis must be added to the device tree. Simply updating the device is not sufficient.


Description of behavior:
The Ttouch-Probe-detection when using the i750 provides inaccurate or completely incorrect values.


Conditions under which the behavior occurs:

  • PLC Designer:  i750 is added to the project with device description V01.01.00.02 is added to the project and
  • TP functionality is used via FB MC_Touchprobe or Homing. 

Affected products:
i750 and PLC-Designer with i750 device description V01.01.00.02


Short-term measures, Recommendations, Rating:
There is already a corrected device description V01.01.00.03. 
For application, see notes under Behavior of the new version.




[Automatic Translation]
URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202300347/1/