Question:
Does the use of the Bus I/O (I/O functionmodul and fieldbus functionmodul) require a controller enable at both modul's?
Answer:
No. The signal 'controller enable' (CINH = terminal X3/28) is not evualated in the fieldbus functionmodul and not transmitted to the I/O functionmodul.
Only the I/O functionmodul require a controller enable at terminal X3/28.
Taxonomy:
8200 motec frequency inverters
,
8200 vector frequency inverters
,
IO module bus FIF E82ZAFBC
AKB-ID:
20010032