i950: EtherCAT fieldbus: Partial error message when switching from INIT to OPERATIONAL state (fixed as of V01.09.01)
Removed from:
Servo-Inverter i950 FW: from V01.09.01
Behavior of the new version: The EtherCAT state 'Operational' is now reliably reached even after multiple state changes via INIT.
Description of behavior: In case of multiple EtherCAT-state changes from OP -> INIT -> OP, the i950 sporadically remains in the ERR SAFEOP state with AL status code 0x001b (Sync Manager watchdog). Bit 0 (watchdog elapsed) is set in parameter 0x2369:000 (EtherCAT error). The described behavior was observed in the field.
Under which conditionsdoes the behavior occur?
EtherCAT communication via the EtherCAT network option
multiple EtherCAT-State change from OP -> INIT -> OP