Network variables are sporadically not updated (fixed with V1.13)

Corrected from:
Cabinet Controller c430 V1.13
Cabinet Controller c520 V1.13
Cabinet Controller c550 V1.13
Behavior of the new version:
Network variables that are assigned values from another controller via UDP communication are updated correctly with new values.


Description of the behavior: 

Network variables that are assigned values from another controller via UDP communication are sporadically not updated with new values.

Conditions under which the behavior occurs:

The behavior can be observed under one of the following conditions

  • A fixed IP address was specified for the broadcast address, e.g.e.g. 192.168.5.5 instead of 192.168.5.255. 
  • The priority of the assigned task is greater than 15.

Affected products:
Cabinet Controller c430
Cabinet Controller c520
Cabinet Controller c550
Short-term measures, Recommendations, Rating:
When using network variables via UDP communication, do not set a fixed IP address as the broadcast address and select a priority lower than 15 for the assigned task.