No encrypted communication possible between PLC Designer and controller via PROFINET interface (fixed with V1.13)
Corrected from:
Cabinet Controller c430 V1.13
Cabinet Controller c520 V1.13
Cabinet Controller c550 V1.13
Behaviour of the new version: Logging in to the Lenze Controllers is also possible via the PROFINET interface. Please note that 'LocalHost' is used in the gateway and a connection via TCP is set when the device is added:
Description of the behavior: It is not possible to log in to the Lenze controller.
Conditions under which the behavior occurs:
The behavior occurs when an encrypted communication between PLC Designer and Lenze controller is to be established via the PROFINET interface.
Affected products: Cabinet Controller c430 from V1.11 Cabinet Controller c520 from V1.11 Cabinet Controller c550 from V1.11
Short-term measures, Recommendations, Rating: For communication between PLC Designer and controller, either use the onboard Ethernet interface of the Lenze controller for encrypted communication or communicate unencrypted via the PROFINET interface.