L_TT1P_StackerCraneHeadControlBase: After ending the repair mode (xMaintenanceMode) via xStop, the SW limits remain deactivated (corrected from V3.24.0)

Corrected from:
Library: L_TT1P_TechnologyModules_LM from V03.24.00
            (Update via EASY Package Manager)

Response of the new version:
The monitoring of the SW limits is now reactivated correctly when leaving the repair mode.
 
What happens?
Function block L_TT1P_StackerCraneHeadControlBase:
Following the use of the repair mode, the monitoring of the SW limits is permanently deactivated.
When operating in another mode, e.g. automatic mode, the monitoring of the SW limits is then switched off.

When does the behaviour occur?
  • The Repair Mode function (xMaintenanceMode = TRUE) is active AND
  • the function is cancelled via xStop.
Which products are affected?
Library:  L_TT1P_TechnologyModules_LM

Short-term measures / Evaluation / recommendations:
If the Repair Mode function is terminated normally, via xMaintenanceMode = FALSE, then the monitoring of the SW limits is reactivated as expected.