Corrected from:
-
Response of the new version:
What happens?
Library manager reports the following error messages:
- Could not open library '#L_SEMP_ErrorManagement'. (Reason: The placeholder library 'L_SEMP_ErrorManagement' could not be resolved.)
- Could not open library '#L_IPAP_ParameterManagerAccess'. (Reason: The placeholder library 'L_IPAP_ParameterManagerAccess' could not be resolved.)
The project cannot be loaded onto the controller.
When does the behaviour occur?
If a PLC project is created based on the ApplicationTemplate (L_FAST_Standard) for the controllers 3200C, p500, c300 or p300 and then the project is saved, the error message described above appears after reopening the PLC project.
Which products are affected?
Application Template V3.23
Short-term measures:
Delete the following libraries from the library manager:
- L_SEMP_ErrorManagement
- L_IPAP_ParameterManagerAccess
Evaluation / recommendations:
When creating a PLC project based on the application template for the Lenze controllers 3200C, p500, c300 and p300, libraries are automatically inserted into the project that are not supported by the target system. After deleting the libraries from the library manager, the PLC project can be opened and compiled without errors.
Automatic Translation