Profinet DP-V1 parameter channel does not restart after restoring Profinet IO communication after a communication fault

Corrected from:
Communication module Profinet IO E94AYCER FV 3.1

Response of the new version:
The Profinet DP-V1 parameter channel is reset internally in the event of a Profinet IO interruption, so that DP-V1 parameter channel communication restarts correctly when communication returns. 
 
What happens?
The Profinet DP-V1 parameter channel does not restart automatically after a Profinet IO communication error - interruption. 
The user must perform a mains switch of the 94xx so that the Profinet DP-V1 parameter channel runs properly again.

When does the behaviour occur?
 If a Profinet IO communication error - interruption occurs, the parameter communication may not restart after the Profinet IO connection is restored.

Which products are affected?
Communication module Profinet IO E94AYCER FV 3.0

Short-term measures:
 none