Question:
What mounting positions are supported by the I/O1000 system and what should be considered?
 
Answer:
For the various mounting positions of the I/O1000 system, the permitted ambient temperatures must be taken into account:
  • Horizontal hanging: 0 ... +60°C
  • Horizontal lying: 0 ... +55°C
  • Vertical: 0 ... +50°C
The number of I/O modules connected to the bus coupler is not restricted by the selected mounting position.
In the vertical mounting position, the bus coupler can be arranged either at the top or at the bottom.