L_TT1P_FlyingSaw: Error "InvalidVelAcc_OffsetScaling" cannot be acknowledged (fixed as of V3.21.0)

Corrected from:
Library L_TT1P_TechnologyModules_LM V3.21.0.6
(Update via EASY Package Manager)
 
Response of the new version:
The error message "InvalidVelAcc_OffsetScaling" at TM L_TT1P_FlyingSawBase(-State) can be acknowledged via input xResetError.

What happens?
 The error message "InvalidVelAcc_OffsetScaling" on TM L_TT1P_FlyingSawBase(-State) cannot be acknowledged via xResetError.

When does the behaviour occur?
One of the following parameters is set to 0 in the parameter structure scPar:
- lrSyncVel , lrSyncAcc, lrSyncDec
- lrPosVel, lrPosAcc, lrPosDec
 
Which products are affected?
Function block L_TT1P_FlyingSawBase(-State) from library L_TT1PTechnologyModules_LM V3.19.0
 
Short-term measures:
In the application, the help function "MAX(Value1, Value2)" can be used to ensure that the parameters are always transferred to the TM with a value greater than zero.
 
Evaluation/Recommendations:
The error described above can be avoided by considering the short-term measures. 

Automatic Translation