Project template 'L_FAST_Standard' contains obsolete EtherCAT master (fixed as of V3.21)

Corrected from:
Project template ApplicationTemplate Standard from V3.21

Response of the new version:
When opening the project template of the Application Template 'L_FAST_Standard' the current EtherCAT Master matching the controller version is inserted automatically.
 
What happens?
The Lenze Safety Controller c250-S cannot be used on the configured EtherCAT master.
 
When does the behaviour occur?
In the project template of the application template 'L_FAST_Standard' the EtherCAT master with version 3.18.1.0 is inserted. For the operation with the c250-S the current version V3.18.2.0 of the EtherCAT Master must be used.
 
Which products are affected?
Project template ApplicationTemplate Standard from V3.20
 
Short-term measures: 
Manually update the EtherCAT master in the PLC Designer project. For this purpose select the EtherCAT master in the device tree of the project and open the context menu (right mouse click). Execute the menu command 'Update device' and select version V3.18.2.0 for the EtherCAT master.
 
Evaluation/Recommendations:
The project template of the Application template contains an obsolete version of the EtherCAT master on which the Lenze Safety Controller c250-S cannot be operated. An application solution is described under 'Short-term measures'.

Automatic Translation

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202000117/1/
Contact form