Corrected from:
L_TT1P_TemperatureControl_LM (V3.15.0.4)
Response of the new version:
The automatic control parameter identification (xIdentCtrlPar = TRUE) is properly completed.
The identified control parameters are very well suited for temperature control and provide excellent results.
What happens?
The automatic identification of the control parameters (xIdentCtrlPar = TRUE) cannot be completed because the maximum temperature has already been reached. The identification has to be aborted.
If the identification is completed, the identified control parameters cannot be used for control. Control is too imprecise.
When does this behaviour occur?
The behaviour occurs when the automatic control parameter identification is started (xIdentCtrlPar = TRUE).
Which products are affected?
L_TT1P_TemperatureControlBase from the L_TT1P_TemperatureControl_LM library (V3.15.0.3 and higher)
Short-term measures:
None