Question:
Which DC-bus voltage thresholds are effective in the 9400 for the undervoltage message (LU) (LU thresholds)?

Answer:
For the 9400, the following fixed undervoltage thresholds are effective for the DC bus voltage depending on the mains voltage selected under C00173:
  • C00173 = 0       (230 V):     LU set = 200 V;   LU reset = 225 V
  • C00173 = 1 (400/415 V):     LU set = 285 V;   LU reset = 430 V (as of device size 8, the LU set threshold is 400 V)
  • C00173 = 2 (460/480 V):     LU set = 490 V;   LU reset = 535 V
  • C00173 = 3       (500 V):     LU set = 540 V;   LU reset = 585 V
  • C00173 = 4       (230 V):     as for 0, but LU threshold can be set under C0174
  • C00173 = 5 (400/415 V):     as for 1, but LU threshold can be set under C0174
  • C00173 = 6 (460/480 V):     as for 2, but LU threshold can be set under C0174
  • C00173 = 7       (500 V):     as for 3, but LU threshold can be set under C0174

If C0173 >= 4, the LU threshold can be variably adapted under C00174.
This is useful if systems shall e.g. be operated on a 400-V and 480-V mains without changing the parameter setting.

For comparison, the LU thresholds of the 9300 series:  
  • C0173 = 0    (<400 V):    LU set = 285 V;   LU reset = 430 V
  • C0173 = 1    (  400 V):    LU set = 285 V;   LU reset = 430 V
  • C0173 = 2    (  400 V):    LU set = 328 V;   LU reset = 475 V
  • C0173 = 3/4 (  460 V):    LU set = 342 V;   LU reset = 490 V