It is not possible to set a response for the communication monitoring between the second master and the communication module

Which products are affected?
MCI Profibus communication module equipped with firmware version 01.00.

What happens?
If a communication error occurs between a second master and the communication module it is not possible to define as response in the drive.

When does the problem occur?
The problem always occurs in case of a communication problem between the second master and the communication module.

Possible diagnostics?
If the communication between the second master and the communication module is interrupted, there is no response initiated or indicated.

Short-term measures/recommendations?
None.

Evaluation:
Since the second master usually is a diagnostic device, the communication interruption is not considered as critical.