Parameter set is not saved in a mode protecting against mains failure

Which products are affected?
Global Drive Loader V3.0

8200 vector
8200 motec
Motor starter starttec

What happens?
After a parameter set download to an 8200 vector, 8200 motec frequency inverter or starttec motor starter the parameter set is not saved in a mode protecting against mains failure by the GD Loader.

When does the problem occur?
The parameter set is not saved in a mode protecting against mains failure after the download if code C0003 was set to 0 (= Do not save the parameter in EEPROM) before the download.

Possible diagnostics?
None.

Short-term measures/recommendations?
Before the parameter set is to be downloaded, carry out mains switching with the 8200 vector, 8200 motec or starttec. As a result, code C0003 of the frequency inverter or motor starter is set to 1 (= Parameter always saved in EEPROM) and the parameter set is automatically saved in a mode protecting from mains failure after the download.

Evaluation:
After mains switching the 8200 vector and 8200 motec frequency inverter or starttec motor starter are always set in such a way that the parameter set is automatically saved when changes have been made. Only if this function is deactivated after switch-on (C0003=0) the GD Loader can save the parameter set in a mode not protecting against mains failure.