PL-Trip, set C0095=1 before trip reset!

Question:
What has to be considered when the error message 'PL-Trip' is reset?

Answer:
Proceed as follows to reset the error message 'PL-Trip' after failed rotor position adjustment:

1. Reactivate the rotor position adjustment via C0095 = 1
2. then execute trip reset and finally
3. execute rotor position adjustment again (rotor position adjustment triggered by controller enable).
Note:
For a successful rotor position adjustment, the motor operating mode (C0006) must be set to synchronous motor (SM).
If a PL-Trip has occurred after a firmware download and an asynchronous motor (ASM) is connected, you nevertheless meanwhile have to switch over to SM to reset the PL-Trip by means of a rotor position adjustment.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200704658/1/