Standardization of the speed setpoint dependent on C0127

Question:
What is the standardization of the analog setpoint dependent on code C0127?

Answer:
In the Lenze factory default setting code C0127 (selection of the setpoint selection) is set to 0. In this setting the analog setpoint can be selected absolutely by means of code C0046 or by means of the process data channel of a bus system. In this case the standardization is: ±24000 ≡ ±480 Hz.
When code C0127 = 1 is set, the analog setpoint is selected in per cent by means of code C0141 or by means of the process data channel of a bus system. The per cent value refers to code C0011 and the standardization is: ±100 % ≡ ±C0011 resp. ±16384 ≡ ±C0011.

Remark:
In chapter 16 of the 8200vector frequency inverter manual this information is shown in the signal flow chart of the function block NSET1.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200602656/1/