Parameter not saved in EEPROM (C0003 = 0)

Question:
When 'Parameter not saved in EEPROM' (C0003 = 0) is selected, is this modification of code C0003 saved in the 8200 vector / motec?

Answer:
No, the setting C0003 = 0 'Parameter not saved in EEPROM' is not saved in the EEPROM of the 8200 vector/motec. This means that after mains connection the setting C0003 = 1 (default setting) 'Parameter always saved in EEPROM' is reactivated and modifications of the code are saved immediately. Therefore, after each mains connection code C0003 = 0 is to be set, when the parameters are not saved in the EEPROM.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200503596/1/
Contact form