CE1, CE2 and CE3 monitoring when CAN status is ¨Warning¨ and ¨Bus Off¨

Question:
Are the monitoring reactions CE1, CE2 and CE3 of bus status 'Warning' or 'Bus Off' activated?

Answer:
No, if the CAN node is in status 'Warning' or 'Bus Off', the process data monitoring for arriving PDO telegrams CE1, CE2 and CE3 are not active. The two states can, however, be monitored by means of range 8200 vector/motec nevertheless. For this purpose in code C0126 the error CE6 is to be parameterized.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200503270/1/