Setpoint is not adopted by the drive controller when selection was made with AIF module

Which products are affected?
8200vector/motec with Appl.-I/O and AIF comunication module (Profibus-DP, CANOpen, ...)

What happens?
If the drive controller is parameterized in a way that the setpoint is preselected by the AIF module (C0001 = 3) and if then linkages of the analog and / or digital input signals (C0410 and C0412) are modified or added in the drive controller, the drive controller possibly does not adopt the preselected setpoint via AIF interface.

When does the problem occur?
The problem occurs when code C0001 = 3 has been set and then linkages of the analog and / or digital input signals (C0410 und C0412) have been modified.

Possible diagnostics?
Code C0005 and/or C0007 is set to 255. By means of the diagnostic function of the function block editor at the AIF-IN-block the setpoint can be displayed which is sent from the AIF module to the drive controller. It is displayed with 0 %, although a setpoint has been preselected by means of the fieldbus.

Short-term measures/recommendations?
After parameter setting of the drive controller set code C0001 to 3 again. The existing signal linkages will not be modified (see article 'Reaction of the drive controller when the selection ¨Setpoint selection¨ is modified (C0001)' (C0001)).

Evaluation:
This incorrect behaviour can be detected during commissioning and can be eliminated by the above-mentioned measure.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200501514/1/