Status display of digital inputs - of the 16-channel module in GDC

Question:
How is the status of the 16-channel module displayed in GDC?

Answer:
In the parameter menu in GDC there is the submenu 'Digital Input' that also has submenus.

Gateway EPM T110 software version 1.0
  • 32 submenus (prepared for maximum stage with 32 modules Digital Input with 8 channels per module)

Gateway EPM T110 software version 1.1
  • 64 submenus (prepared for maximum stage with 32 modules Digital Input with 16 channels per module)

Within one submenu, e. g. 'Digital Input Module 1' the status of the first module is displayed from the gateway point of view in the index 6000h Sub 001. These status information contain 1 Byte.

If a 16-channel module EPM-T211 is used, the status of the first Bytes of the module is displayed in this submenu 'Digital Input Module 1' in index 6000h Sub 001. The status display of the second Byte is made in submenu point 'Digital Input Module2' in the index 6000h Sub 002.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200501193/1/