Minimum frequency is larger than or equal to maximum frequency (C0010 ≥ C0011)

Question:

How does the 8200vector/motec frequency inverter respond if the minimum output frequency (C0010) is parameterised larger than or equal to the maximum output frequency (C0011)?

Answer:

If code C0010 (minimum output frequency) is parameterised equal to or larger than code C0011 (maximum output frequency) the 8200vector/motec frequency inverter (as of software version 3.5) does not indicate a rotating field frequency for the motor if the motor is enabled (terminal 28 = HIGH signal) and the setpoint is selected via analog input 1. This software controller inhibit has been implemented as of software version 3.5 since a change of the direction of rotation may have occurred in case of previous software versions. This can be excluded now.

If the setpoint is selected via JOG values in case of the parameter setting mentioned before the motor rotates with the set frequency.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/200409420/1/
Contact form